Full Site
Publications
Energy Policy
Programs
Press and Media
Consumer Resources
Publications and Meetings
Support
 
Online Guide to Energy-Efficient Commercial Equipment --> High-Performing HVAC Systems --> Air-Handling Systems

Online Guide to Energy-Efficient Commercial Equipment

Air-Handling Systems


Air-handling systems consist of the fans, filters, dampers, and ducts that deliver cooled or heated air throughout a building. The fans required are included in packaged equipment, except when separate powered exhaust is required to balance the pressure contribution of the incoming ventilation air. Fans are separately specified for built-up central systems. Alternative systems can be compared along several dimensions: their fan energy requirement; the degree to which they can respond to heating and cooling needs of different building zones; and their ability to take advantage of cooler outside air or water through economizers or to supply reheat energy for temperature control to zones in the building. In general, more flexible systems cost more to install but are often more efficient on a system basis, and provide greater comfort for building occupants.



Economizers

In most commercial applications, at least some interior spaces need cooling during times when the outdoor air temperature and humidity are sufficiently low to economically provide cooling without using the mechanical refrigeration cycle. Economizers use controls and supply and return air dampers to control outside air quantities. Economizers are an option for virtually all packaged air-conditioning equipment. However, for very small units and in some climates, economizers may not be economical. When bringing in large quantities of outdoor air, equivalent quantities of indoor air must be exhausted at the same time. This exhaust is called "relief air."

At some upper outside temperature limit, it is no longer economical to bring in 100 percent outdoor air because the energy to cool it will be greater than cooling the building return air mixed with the minimum quantity of outdoor air. This point is called the economizer changeover point and, depending on the climate, there are several ways to determine and control the changeover.

  • Fixed dry bulb controls shift from economizer to refrigeration cycle at a specific outdoor temperature, such as 75°F maximum outside temperature.
  • Differential dry bulb systems compare the dry bulb temperature of the outdoor air to the dry bulb temperature of the return air and make the changeover when the outdoor temperature is near the return temperature. Dry bulb systems are appropriate in dry climates, but may cause problems where high humidity and moderate to high outdoor temperatures occur together.
  • For these situations (such as the climate belt from Houston through the Southeast and into the Mid-Atlantic states), "enthalpy" controls are better, since they consider the work required to dehumidify the outdoor air. (Enthalpy is a measure of the total heat in the air, made by measuring both the dry bulb temperature and the relative humidity.)

    • Fixed enthalpy controls work like fixed dry bulb controls, except they consider the enthalpy of the outdoor air (in Btus per pound of air) rather than the dry bulb temperature.

    • Differential enthalpy controls compare the enthalpy of the outdoor air with the enthalpy of the return air and change from economizer/outside air to refrigeration whenever the outdoor air enthalpy is greater that the return air enthalpy. In humid climates, the added cost and complication of the enthalpy controller will generally be justified by increased comfort and energy savings.


Ventilation Air and Energy Efficiency

As a bonus, during economizer operation abundant outside air is brought into the space, diluting and exhausting contaminants generated there. However, unlike residential applications, most commercial applications require the HVAC system to bring in, condition, and distribute specified amounts of outdoor air for ventilation at all times that the space is occupied. This means that some form of outdoor air intake must be integrated into the design of the system. It is important to know what the outdoor air requirements are for the space being conditioned. For example, restaurant kitchens need to exhaust large quantities of air through cooking hoods. Some applications require so much ventilation air that the need cannot be met with conventional packaged equipment, or economically met by built-up systems. In these cases, energy recovery ventilation, heat recovery ventilation, or air-to-air heat exchange is needed. These devices use desiccants, heat pipes, or other technologies to recover energy from the exhaust air and transfer it to the outdoor supply air. In winter, they use this energy to preheat the incoming air by cooling the exhaust air, and the opposite in summer. These devices can save enormous amounts of energy (U.S. Department of Energy. 1999.). However, they also can waste energy if not carefully engineered. For example, devices that have high peak load efficiency may have so much pressure drop that at part load they require more electricity for their fans than they save in cooling. Such situations required engineered solutions that may raise first costs.


Dehumidification

If the indoor temperature rises above the temperature set point, the thermostat energizes mechanical cooling; if temperature drops, cooling is de-energized. If the unit is properly sized, the cooling will be running most of the time during extremely hot weather conditions. Since most days are not extreme, under normal conditions the mechanical cooling cycles on and off to maintain the desired temperature. As the unit only dehumidifies when the mechanical cooling is energized and has run long enough to cool the evaporator coil, it is not uncommon for spaces to be uncomfortably humid for many hours each year.

A simple way to help the unit do more dehumidification is to reduce the supply fan speed (being careful not to violate ventilation requirements.) This can be accomplished with fan speed switches, changing drive pulleys, or variable speed fans. This both cools the coil (increasing condensation) and lets the unit operate longer, providing additional dehumidification. Another option is to install humidity controls that override the temperature controls. If the relative humidity exceeds control levels, the humidistat energizes the cooling mode, enabling dehumidification. Where necessary, there are several options for warming the dehumidified air for increased comfort. Some are inefficient (e.g., resistance reheat or hot water coils), and others have lower energy penalties (e.g., hot gas reheat or downstream air-to-air heat exchangers)

Alternatively, desiccant dehumidifiers are viable in some applications. Desiccants naturally attract moisture, efficiently removing latent (humidity-related) load from the air. Conventional air conditioners are then typically used to reduce the temperature (called the sensible load) of the dried air to desired occupant comfort levels. Latent and sensible loads are handled more efficiently because each component is optimized to independently remove these loads. When heated, the saturated desiccant is regenerated to be used again (Slayzak, Pesaran, and Hancock. 1996. Experimental Evaluation of Commercial Desiccant Dehumidifier Wheels. Golden, Colo.: National Renewable Energy Laboratory).

Commercial desiccant dehumidification systems have been applied primarily in supermarkets and hotels and motels. In supermarkets they displace antisweat heaters and defrosters that consume considerable energy to control moisture levels in freezer display cases. The systems also have been used to effectively control humidity levels in hotels and motels, where mold and mildew can damage wallpaper, paint, carpet, and other materials. In addition, desiccant systems can improve indoor air quality, improve ventilation rates, and remove air pollutants and odors (National Renewable Energy Laboratory. 2000. Desiccant Cooling: A Non-CFC, Energy-Efficient Space-Conditioning Technology. Golden, Colo.: National Renewable Energy Laboratory).


Constant Volume Systems

Single zone: The most commonly applied air-handling system is a constant volume, single-zone system-just like a house with one thermostat in an "average" location controlling the air delivered to every room. Packaged air-conditioning units of all sizes are available as constant volume, single-zone units, as are heated fan coils and water-loop heat pumps. As the name implies, this equipment is characterized by a single space thermostat that controls temperature and a fan that delivers a constant volume of heated or cooled air (not a mixture of the two) to every space. Some constant volume, single-zone systems (e.g., packaged rooftop units) can easily integrate air-side economizers to take advantage of "free" cooling but usually there is no reheat in these systems for temperature control. Of the three systems presented here, fan energy for constant volume, single-zone systems is generally the highest. Fan energy could be reduced if the fan were allowed to cycle with calls for heating and cooling; however, this practice is regulated by most standards and building codes, in order to maintain ventilation by outside air. These systems can cause discomfort under rather common conditions. Consider a system that is designed to meet 95ºF outdoor conditions. When it is 80ºF outside, the refrigeration system will cycle off and on. But the circulation fan runs full-time to bring in outdoor air and mix it with the air returned from the system. In the summer, the system will distribute much warmer (and often much more humid) air when the fan is on but the compressor is off.

Multizone: Constant volume, multizone systems were designed to provide simultaneous heating and cooling to multiple temperature control zones from a single packaged unit. Individual temperature control zones receive air from two ducts, one equipped with a heating coil (or another heating method, such as a small gas furnace) and the other with a cooling coil. The space thermostat energizes either the heating coil or the cooling coil as needed to maintain the space temperature. These systems, which were widely applied 20 to 30 years ago, are very inefficient because they mix heated and cooled air streams for space temperature control. They can be very expensive because of the need for two duct systems, each sized to meet virtually the entire load.


Variable Air Volume Systems

Variable air volume (VAV) systems can be very efficient if well designed and carefully operated. These systems vary the amount of air supplied to a space, rather than leaving the supply volume constant and varying the temperature of the air, as with constant volume systems. Typically, these systems are more efficient since: (1) less energy is used for cooling because the volume of air cooled is reduced; (2) less energy is required for heating because less air needs to be reheated; and (3) fan energy is reduced because the amount of air the fan needs to move is reduced. These systems generally employ economizers.

Variable air volume, variable temperature systems have been applied to packaged equipment to overcome the constant volume, single-zone system's lack of zone control. One thermostat is acceptable as long as the zone served has uniform heating or cooling demands. But this is seldom the case. The boss' office is much too cold or the conference room is much too warm. Fortunately, in variable air volume, variable temperature systems, a given area is served by a single unit but the area is divided into temperature control zones and each zone gets a thermostat. Each thermostat operates an automatic control damper located in the branch duct that serves the zone. In the cooling mode, if the zone is too cold, the damper is closed. If the zone is too warm, the damper is opened. Just the opposite occurs in the heating mode. All the thermostats "talk" to a central panel that decides which zone demands the most heating or cooling. Based on this decision, the central panel operates the unit. By not allowing the dampers to close fully, ventilation requirements can be met. However, with these systems it is critical that all zones have comparable loads, so some are not calling for heating while others require cooling.

 
Energy Policy | Programs | Press & Media | Consumer Resources
Publications & Meetings | Support ACEEE | Site Map | Home

© American Council for an Energy-Efficient Economy.
All Rights Reserved.
Read our Copyright and Permission requests information.
Read our privacy guidelines. Contact us.