|
Contemporary
HVAC controls automatically regulate system output. At minimum,
these controls maintain indoor temperature as interior loads
and outdoor conditions change. In a small heating-only building,
this is done with a thermostat that "compares" indoor
temperature with an occupant-selected "setpoint,"
or desired value. When the indoor temperature drops enough,
the thermostat activates the furnace or boiler, and then turns
it off when the space reaches the setpoint. The difference
between the "start" and setpoint temperatures is
the "dead band." If it is set too large, temperatures
will vary too much for comfort. If it is too small, the equipment
will tend to run in very short cycles, which is very inefficient.
Even the simplest systems require judgments to optimize performance.
Conceptually,
air conditioning requires a second controller, although usually
it is integrated into the same thermostat box. The thermostat
controls the A/C compressor as well as the furnace section
and air handler (fan). From this point, residential systems
also can have controls that become much more complex, even
though the external appearance is still "just" a
thermostat. In addition to programmable settings (for different
days or times of day), some advanced units have separate controls
driven by humidity levels.
Controls for smaller commercial unitary equipment are quite
similar to residential units, except that the equipment should
bring in outdoor air to comply with the ventilation standards
of ASHRAE Standard 62.1 (discussed further below) (American
Society of Heating, Refrigerating, and Air-conditioning Engineers.
2001. Standard 62-2001-Ventilation
for Acceptable Indoor Air Quality (ANSI Approved).
Atlanta, Ga.: American Society of Heating, Refrigerating,
and Air-conditioning Engineers).
This
equipment may also include an economizer that brings in large
amounts of outdoor air when it is sufficiently cooler than
the indoor air, thus providing cooling at lower cost than
operating the refrigeration system. Economizers
are crucial, except where the daily and seasonal temperature
swings are very small.
Buildings
with larger, multi-zone, and multi-unit packaged systems,
and those with central systems, are almost always controlled
by an energy management system (EMS) with a direct digital
controller (DDC). These use zone thermostats, outdoor temperature,
and other sensors to determine how to operate all the equipment
to provide economy and comfort. Their design, installation,
and troubleshooting are generally done by specialist firms.
For a large building, it is challenging just to develop a
bid specification for an energy management system that can
be expected to work correctly! At the level of the building
operator, modern systems will typically include features such
as:
- Night
Setback: This turns off the fans, closes the ventilation
dampers, and shuts down the heating and cooling equipment,
except as needed to keep the building warm enough or cool
enough to return to operating conditions in the morning.
- Seven
Day Programming: This keeps track of the day of the week
and allows the night setback to continue on Saturdays and
Sundays, and offers holiday overrides.
- Optimal
Start: When the space switches from unoccupied to occupied,
the equipment must go through a warm-up or cool-down period.
The optimal start feature recognizes both the outdoor condition
and the space temperature and delays the starting of the
equipment in the warm-up or cool-down mode as long as possible
while still achieving occupied temperature conditions at
the desired time.
- Discharge
Air Limit: A thermostat can be placed in the unit to limit
the temperature of the discharge air during the economizer
mode. This is a safety feature that will ensure that the
air temperature is not too cold for occupant comfort.
|