|
Once
the efficiency of the motor is addressed, it is important
that it be installed in such a way that the energy efficiency
potential of the motor is realized and reliability is maximized.
As noted at the beginning of this chapter, the system may
account for a greater share of the energy use characteristics
than the motor itself. The installation parameters considered
in this section include motor speed, shaft alignment, electrical
supply, and motor operating characteristics.
Motor
Speed
The
first thing to check when installing any new motor is its
operating speed. While (on average) energy-efficient motors
have higher full-load speeds than standard motors, there is
a significant variation in speed within all types of motors.
Installing a motor with a higher operating speed can result
in increased energy consumption on centrifugal loads (e.g.,
fans and pumps). This speed change can sometimes lead to overloading
of the motor, which can result in premature failure.
Ideally,
the first step in the replacement process is to characterize
the actual load requirements. This determination frequently
requires monitoring and engineering analysis, and as a result
is only justified for major applications. At a minimum, the
operating speed of the equipment with the new motor should
be as close to the old motor as possible. For belt-driven
equipment, the speed difference can be compensated for by
changes in pulley size. The flow of direct-drive pumps can
be adjusted by trimming impellers. These approaches are a
low cost, preferred solution to maintaining speed for constant
load applications.
If a
more complete characterization is desired, it should include
whether the present flow (air or water) is correct and whether
there is any significant variation in the flow requirements.
As an example, for a main HVAC distribution fan, the temperature
rise/drop across heat exchanger and register discharge pressure
should be measured to determine if the flow is appropriate
to the equipment design specifications. Dampers should be
checked to ensure that they are not substantially closed.
If the flow is varied by dampers, the maximum and minimum
flows should be measured and an estimate of the frequency
of the flow change made. If the ratio between maximum and
minimum flow is greater than two to one, some means of varying
the motor speed should be considered.
For fluctuating
loads with significant annual run times, an adjustable speed
drive should be considered. These devices allow the motor
speed to be varied to follow the load and thus minimize energy
consumption. ASDs can more than double motor system cost but
the energy savings from properly designed applications can
be impressive, sometimes exceeding 50 percent. If the load
is not continually varying but is operated in two specific
operating regimes (e.g., a HVAC system with a lower flow requirement
during heating and a higher requirement during the cooling
season), there are other less costly options that can be considered.
Dual pulleys can be installed on the motor and fan drive-shafts,
and the speed can be changed manually as part of the seasonal
change-over (although these options are generally available
only in standard-efficiency models). In some applications,
a two-speed motor may be an option. (A multi-speed motor has
multiple windings allowing the motor to be operated at two
or more different speeds by switching how the electricity
is supplied to the motor.) In general, these motor are less
efficient and more costly than single-speed motors but the
energy savings from reduced operating speed will frequently
make this an attractive option.
ASDs
have gained an undeserved reputation for unreliability. Most
of these problems can be traced to problems with the electrical
supply (discussed below) or a mismatch between the drive and
motor. If the drive and motor are not electrically compatible,
harmonics can cause the motor to overheat or experience excessive
vibration, both of which will lead to premature failure. These
problems can be avoided by checking with the motor and drive
manufacturers before installing the ASD. To address this potential
problem, many of the motor manufacturers are now offering
matched motor/ASD packages. EPRI
and BestPractices
Motor Systems are now making available a design and
selection tool, ASDMaster.
Alignment
Proper
motor-shaft alignment reduces motor load and extends bearing
life, and increases the torque delivered to the load. Perfectly
aligned motors lose less than 1 percent of transmitted torque
while each degree of misalignment increases torque loss by
1 percent. Beyond 5 degrees, bearing failure results. Misalignment
is in fact the leading cause of bearing failure. Most coupling
and transmission systems allow for some flexing but this flexing
among the components results in increased friction that robs
the load of torque and produces energy losses.
The best
shaft alignment procedure involves first securing the driven
equipment, then working back to the motor. The recommended
alignment tolerance is 5/1,000 of an inch at the coupling
but many experts feel that the tolerance should be measured
at the bearings for a more precise alignment. For maximum
energy and reliability benefit, however, the misalignment
should be as close to zero as possible.
There
are a number of alignment methods in use ranging from a crude
"straight edge" method, to dial indicators, to laser alignment.
The straight edge method is appropriate only for low speed
(i.e., no greater that 300 rpm) and belt systems where other
alignment methods are impractical. The dial indicator method
is the most widely used and with appropriate attention to
detail produces good results for all systems except high-speed
equipment (i.e., about 3,600 rpm) where the greater cost of
the laser systems is required (Energy-Efficient
Motor Systems Handbook).
Electrical
Supply
The equipment
that supplies electricity to motor systems can produce energy
losses and adversely affect the reliability and life of the
motor. Ideally, the electricity driving a motor should be
at the design voltage and frequency, and have a sinusoidal
wave form. Unfortunately these conditions frequently are not
met. These deficiencies can adversely affect both the efficiency
and the life of the motor.
System
deficiencies fall into the following four broad categories:
- Voltage
imbalances in three-phase systems;
- Excessively
high or low system voltage;
- Low
power factor; and
- Power
quality problems (most frequently voltage transients and
harmonics).
Voltage
imbalances can result from imbalanced circuits in the facilities,
frequently resulting when single-phase lighting is all operated
off a single leg of the primary three-phase service. In some
cases, the phase imbalance may result from problems in the
utility supply system, especially if the facility is relatively
far from the nearest substation. Transient imbalances, or
loss of one or two phases, can result from a utility equipment
failure such as the loss of a transformer. This problem, often
referred to as "single phasing," often occurs due to lighting
strikes and can result in electrical failure of the motor.
Devices called phase monitors are available that measure the
differences between the phases and will shut down the circuit
if the difference reaches levels that can cause damage. If
a facility is in an area prone to outages, such as rural areas,
these devices should be considered for large motors and expensive
devices such as refrigeration compressors.
One solution
to many under-voltage conditions is to increase the size of
cabling. In addition to reducing voltage drops in the cable,
the increased conductor diameter has the added benefit of
reducing line losses. Low power factor can be corrected by
using capacitors connected to the motor or at the point of
electricity distribution. Improving system power factor yields
significant electricity bill savings by reducing utility charges
for low power factor. It can also result in electricity savings
by reducing line currents, which in turn reduce cable and
transformer losses (Dorhofer, F.J., and W.H. Heffington. 1994.
"Electrical Energy Monitoring
in an Industrial Plant." In Proceeding of the 16th
National Industrial Energy Technology Conference, 269-274.
Houston, Tex.: Texas A&M University.). Power quality problems
can result from electricity supply problems external to the
facility but are frequently associated with equipment at the
facility such as switching power supplies used in adjustable
speed drives and computers. Various types of filters and surge
suppressors can be used to address these problems but if the
problem is not correctly identified, the solution can make
the problem worse. As a result, a technician experienced with
these problems is required to correctly diagnose the problem
and propose the correct solution. Many utilities have developed
teams of experts to help deal with these problems in customer
facilities.
ACEEE
has estimated that improvements to electric supply systems
can result in a 1 to 5 percent savings in motor loads, along
with improved reliability and extended motor life. Many of
these improvements will also result in additional energy savings
and improved reliability in non-motor electrical loads (Energy-Efficient
Motor Systems Handbook).
Operating
Characteristics
Some
efficient motors may cause breakers to trip because they have
a higher starting current spike. This current is too short
lived to trip hybrid or thermal breakers but may cause problems
with magnetic breakers. If magnetic breakers trip, the problem
can be addressed by adjusting the set point on the breakers
or by replacing the breakers with new models.
Energy-efficient
motors meet the torque requirements specified in NEMA Design
B but may not exceed the specifications by as much as many older
motors. As a result, a premium-efficiency motor used in an application
in which torque requirements substantially exceed Design B specifications
may not be able to handle the load, while an older design may
be able to operate in the greater-than-specification condition.
For these applications, examine why the high starting torque
is required or consider Design A motors with higher starting
torque. For more information, see ACEEE's Energy-Efficient Motor Systems Handbook. |